248 lines
6.6 KiB
YAML
248 lines
6.6 KiB
YAML
|
substitutions:
|
||
|
node_name: "cms-boiler-monitor"
|
||
|
node_verbose_name: "Boiler Monitor"
|
||
|
|
||
|
packages:
|
||
|
cms: !include packages/cms-general.yaml
|
||
|
|
||
|
esp32:
|
||
|
board: lolin_s2_mini
|
||
|
|
||
|
status_led:
|
||
|
pin: GPIO15
|
||
|
|
||
|
uart:
|
||
|
tx_pin: 11
|
||
|
rx_pin: 10
|
||
|
baud_rate: 38400
|
||
|
|
||
|
modbus:
|
||
|
|
||
|
modbus_controller:
|
||
|
id: boiler1
|
||
|
address: 0x1
|
||
|
setup_priority: -10
|
||
|
update_interval: 30s
|
||
|
|
||
|
text_sensor:
|
||
|
## Trend Status ##
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: Demand source
|
||
|
address: 0x0006
|
||
|
register_type: read
|
||
|
raw_encode: HEXBYTES
|
||
|
lambda: |-
|
||
|
uint16_t value = modbus_controller::word_from_hex_str(x, 0);
|
||
|
switch (value) {
|
||
|
case 0: return std::string("Unknown");
|
||
|
case 1: return std::string("No source demand");
|
||
|
case 2: return std::string("CH");
|
||
|
case 3: return std::string("DHW");
|
||
|
case 4: return std::string("Lead Lag slave");
|
||
|
case 5: return std::string("Lead Lag master");
|
||
|
case 6: return std::string("CH frost protection");
|
||
|
case 7: return std::string("DHW frost protection");
|
||
|
case 8: return std::string("No demand due to burner switch (register 199) turned off");
|
||
|
case 9: return std::string("DHW storage");
|
||
|
case 10: return std::string("Reserved");
|
||
|
case 11: return std::string("Warm weather shutdown");
|
||
|
case 12: return std::string("Hot standby");
|
||
|
}
|
||
|
return x;
|
||
|
|
||
|
|
||
|
## BURNER CONTROL STATUS ##
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: Burner control status
|
||
|
address: 0x0020
|
||
|
register_type: read
|
||
|
raw_encode: HEXBYTES
|
||
|
lambda: |-
|
||
|
uint16_t value = modbus_controller::word_from_hex_str(x, 0);
|
||
|
switch (value) {
|
||
|
case 0: return std::string("Disabled");
|
||
|
case 1: return std::string("Locked out");
|
||
|
case 4: return std::string("Anti-short cycle");
|
||
|
case 5: return std::string("Unconfigured safety data");
|
||
|
case 34: return std::string("Standby Hold");
|
||
|
case 35: return std::string("Standby Delay");
|
||
|
case 48: return std::string("Normal Standby");
|
||
|
case 49: return std::string("Preparing");
|
||
|
case 50: return std::string("Ignition");
|
||
|
case 51: return std::string("Firing");
|
||
|
case 52: return std::string("Postpurge");
|
||
|
}
|
||
|
// Reserved
|
||
|
return x;
|
||
|
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: Lockout code
|
||
|
address: 0x0022
|
||
|
register_type: read
|
||
|
raw_encode: HEXBYTES
|
||
|
lambda: |-
|
||
|
uint16_t value = modbus_controller::word_from_hex_str(x, 0);
|
||
|
switch (value) {
|
||
|
case 0: return std::string("No lockout");
|
||
|
// TODO: see Table 9
|
||
|
}
|
||
|
return x;
|
||
|
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: Alarm reason
|
||
|
address: 0x0023
|
||
|
register_type: read
|
||
|
raw_encode: HEXBYTES
|
||
|
lambda: |-
|
||
|
uint16_t value = modbus_controller::word_from_hex_str(x, 0);
|
||
|
switch (value) {
|
||
|
case 0: return std::string("None");
|
||
|
case 1: return std::string("Lockout");
|
||
|
case 2: return std::string("Alert");
|
||
|
case 3: return std::string("Other");
|
||
|
}
|
||
|
return x;
|
||
|
|
||
|
## CENTRAL HEATING (CH) STATUS ##
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: CH status
|
||
|
address: 0x0040
|
||
|
register_type: read
|
||
|
raw_encode: HEXBYTES
|
||
|
lambda: |-
|
||
|
uint16_t value = modbus_controller::word_from_hex_str(x, 0);
|
||
|
switch (value) {
|
||
|
case 0: return std::string("Unknown");
|
||
|
case 1: return std::string("Disabled");
|
||
|
case 2: return std::string("Normal");
|
||
|
case 3: return std::string("Suspended");
|
||
|
}
|
||
|
return x;
|
||
|
|
||
|
|
||
|
## PUMP STATUS ##
|
||
|
# TODO: map to text (bitmap)
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: Pump A status
|
||
|
address: 0x005D
|
||
|
register_type: read
|
||
|
raw_encode: HEXBYTES
|
||
|
|
||
|
# TODO: map to text (bitmap)
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: Pump B status
|
||
|
address: 0x005E
|
||
|
register_type: read
|
||
|
raw_encode: HEXBYTES
|
||
|
|
||
|
## LEAD LAG STATUS ##
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: "Lead Lag master status"
|
||
|
address: 0x00A0
|
||
|
register_type: read
|
||
|
raw_encode: HEXBYTES
|
||
|
lambda: |-
|
||
|
uint16_t value = modbus_controller::word_from_hex_str(x, 0);
|
||
|
switch (value) {
|
||
|
case 0: return std::string("Unknown");
|
||
|
case 1: return std::string("Disabled");
|
||
|
case 2: return std::string("Normal");
|
||
|
case 3: return std::string("Suspended");
|
||
|
}
|
||
|
return x;
|
||
|
|
||
|
# TODO: map to text (bitmap)
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: "Lead Lag slave status"
|
||
|
address: 0x00A1
|
||
|
register_type: read
|
||
|
raw_encode: HEXBYTES
|
||
|
|
||
|
# Derived from "SOLA Modbus I/F" Rev. 4.1.1
|
||
|
# https://www.ccontrols.com/support/dp/OEMModbusSIS4_1_1_1_1.pdf
|
||
|
sensor:
|
||
|
## Trend Status ##
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: Outlet (S3S4) or Outlet limit (S3) sensor
|
||
|
address: 0x0007
|
||
|
register_type: read
|
||
|
value_type: U_WORD # U16
|
||
|
unit_of_measurement: '°C'
|
||
|
accuracy_decimals: 1
|
||
|
filters:
|
||
|
- multiply: 0.1
|
||
|
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: Inlet (S1) sensor
|
||
|
address: 0x000B
|
||
|
register_type: read
|
||
|
value_type: U_WORD # U16
|
||
|
unit_of_measurement: '°C'
|
||
|
accuracy_decimals: 1
|
||
|
filters:
|
||
|
- multiply: 0.1
|
||
|
|
||
|
|
||
|
## STATISTICS ##
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: Burner cycle count
|
||
|
address: 0x0080
|
||
|
register_type: read
|
||
|
value_type: U_DWORD # U32
|
||
|
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: Burner run time
|
||
|
address: 0x0082
|
||
|
register_type: read
|
||
|
value_type: U_DWORD # U32
|
||
|
unit_of_measurement: h
|
||
|
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: CH pump cycle count
|
||
|
address: 0x0084
|
||
|
register_type: read
|
||
|
value_type: U_DWORD # U32
|
||
|
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: System pump cycle count
|
||
|
address: 0x0088
|
||
|
register_type: read
|
||
|
value_type: U_DWORD # U32
|
||
|
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: Boiler pump cycle count
|
||
|
address: 0x008A
|
||
|
register_type: read
|
||
|
value_type: U_DWORD # U32
|
||
|
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: Controller cycle count
|
||
|
address: 0x008E
|
||
|
register_type: read
|
||
|
value_type: U_DWORD # U32
|
||
|
|
||
|
- platform: modbus_controller
|
||
|
modbus_controller_id: boiler1
|
||
|
name: Controller run time
|
||
|
address: 0x0090
|
||
|
register_type: read
|
||
|
value_type: U_DWORD # U32
|
||
|
unit_of_measurement: h
|